In a variable-primary-flow chilled water plant (no decoupler bypassing full flow in idea), a VFD on the chiller pump is primarily modulated to maintain what, subject to chiller mfr limits?
Choices
- (A) Refrigerant GWP 0 by law
- (B) Duct FPM at grille only
- (C) Domestic 60 psi at faucet
- (D) Required ΔT and/or minimum/bounded flow and acceptable lift through chiller, per mfr+controls
Correct answer: (D)
Required ΔT and/or minimum/bounded flow and acceptable lift through chiller, per mfr+controls
Explanation
VPF: chiller mfr min flow; DP or ΔT control at plant.